General Description

The detector has wide-angle sensitivity that can reliably and quickly detect weak ultraviolet radiations emitted by flame. It will not react to room illuminations, infrared or other light sources unrelated to real fire.

Applications

  • Premises with higher ceilings: theater, gym, storage, gallery or warehouse, etc.
  • Places where fires happen easily: places storing with combustible goods, gas stations, factory working places, machine rooms, etc.
  • Ventilate places: open markets, station platforms, hotel lobbies, department stores, etc. (places that smoke and heat can not gather during early period of fire)
  • Others: tunnels, computer rooms, etc.

Installation Instructions

  • Install at obstruction-free places.
  • Avoid installing near mercury lamps, halogen lamps and sterilization lamps.
  • Avoid installing within sensitive range of welding sparks and radiation.

Approval

Specification

AH-0014 Flame Detector

Model AH-0014
Type 2 wire 3 wire 4 wire
Alarm Contact N/A   N/A 0.8A @30V DC, 0.4A @125V AC
Voltage Range 12 ~ 30V DC
Alarm Current @24V DC 470Ω 40mA 40mA 35mA
Standby Current @24V DC 470Ω under 100μA
Sensor Type  Ultraviolet
Sensitivity Angle 120°
Sensitivity Range It can detect flame of 15mm at distance of 3m
Ambient Temperature -10 ~ +55
Material Fire-proof plastic
Dimensions 111mm(Dia.) x 47mm(H)
Weight About 170g
Color White