Description

The detector has wide-angle sensitivity that can reliably and quickly detect weak ultraviolet radiations emitted by flame. It will not react to room illuminations, infrared or other light sources unrelated to real fire.

Installation Instructions

  • Install at obstruction-free places.
  • Avoid installing near mercury lamps, halogen lamps and sterilization lamps.
  • Avoid installing within sensitive range of welding sparks and radiation.

Applications

  • Premises with higher ceilings: theater, gym, storage, gallery or warehouse, etc.
  • Places where fires happen easily: places storing with combustible goods, gas stations, factory working places, machine rooms, etc.
  • Ventilate places: open markets, station platforms, hotel lobbies, department stores, etc. (places that smoke and heat can not gather during early period of fire)
  • Others: tunnels, computer rooms, etc.


Specifications

Model
AH-0014
Type
2-wire
3-wire
4-wire
Alarm Contact
N/A
N/A
0.8A @30V DC
0.4A @125V AC
Voltage Range
12 ~ 30V DC
Alarm Current
@24V DC 470£[
35mA
35mA
30mA
Standby Current
45£gA
Sensor Type
Ultraviolet
Sensitivity Angle
120¢X
Sensitivity Range
It can detect flame of 15mm at distance of 3m
Ambient Temperature
-10¢J ~ +55¢J
Material
Fire-proof plastic
Dimensions
111mm(Dia.) x 47mm(H)
Weight
About 170g
Color
White



Approval

 


 

 


HORING LIH INDUSTRIAL CO., LTD.
4F., NO. 18, Lane 327, Chung Shan Road, Sec. 2,
Chung Ho 235, Taipei Hsien, Taiwan
Tel: +886 2 22487599      Fax: +886 2 22407752
E-mail: ahtaipei@ms26.hinet.net

 


European Office
Tel: +46 8 6426314 +372 671 5039
Fax: +46 8 6420235 +372 671 5040
E-mail: info@horing-europe.com   ao@qts.ee